FUNCTIONS AND FEATURES
l The input can be freely selected as thermocouple, RTD, voltage, current, etc. There’s a non-linear correction table inside, and no need for correction.
l Adopts advanced modular structure, provides various kinds of output specifications and meeting a wide range of applications.
l Humanized operation method, easy to learn and use.
l With standard PID, AI artificial intelligence adjustment APID, MPT and other adjustment methods, and excellent control characteristics including self-tuning, self-learning function, no overshoot and no undershoot.
l Equipped with power-off alarm function to avoid false alarms when powered on.
l Support RS485 or RS232 communication interface, can be used as the lower machine for AIDCS, split paperless recorder and touch screen control system.
l AI-516P/526P has program control function and adopts AI artificial intelligence adjustment algorithm with a curve fitting function to obtain a smooth curve control effect.
l Anti-interference performance meets the requirements of electromagnetic compatibility under harsh industrial conditions.
MODEL SELECTION AND SPECIFICATIONS
AI- | □ | □ | □ | □ | □ | □ | □ | □ |
| Specifications |
Model | 516 |
|
|
|
|
|
|
|
| multiple modules output, support AIBUS/ MOSBUS protocols |
516P |
|
|
|
|
|
|
|
| based on AI-516, 30 segments programmable function is added |
519 |
|
|
|
|
|
|
|
| hand-auto switching function |
526 |
|
|
|
|
|
|
|
| Heating/ cooling dula PID output, limitation of ramp rate, time input selection |
526P |
|
|
|
|
|
|
|
| based on AI-526, 30 segments programmable function is added |
Panel size | A |
|
|
|
|
|
|
| 96*96*100mm |
A2 |
|
|
|
|
|
|
| 96*96*100mm, with 25 segments and 4 levels of luminosity |
B |
|
|
|
|
|
|
| 160*80*100mm |
B2 |
|
|
|
|
|
|
| 160*80*100mm, with 25 segments and 4 levels of luminosity |
C |
|
|
|
|
|
|
| 80*160*100mm |
C3 |
|
|
|
|
|
|
| 80*160*100mm, with 50 segments and 2 levels of luminosity |
D |
|
|
|
|
|
|
| 72*72*95mm |
D2 |
|
|
|
|
|
|
| 48*48*95mm (10 terminals) |
D6 |
|
|
|
|
|
|
| 48*48*95mm (12 terminals) |
E |
|
|
|
|
|
|
| 48*96*100mm |
F |
|
|
|
|
|
|
| 96*48*100mm |
Multiple input (MIO) | I2 |
|
|
|
|
|
| ON-OFF input module for dual SV switch or run/stop program |
I4 |
|
|
|
|
|
| 2-wire transmitter or 4-20mA signal input, provide 24VDC to transmitter |
V* |
|
|
|
|
|
| V24, V12, V10 is for 24VDC, 12VDC, 10VDC power supply module |
Output (OUTP) | L1 |
|
|
|
|
| large volume relay contact output (250VAC/2A) (Chinese brand) |
L2 |
|
|
|
|
| small volume relay contact output (250VAC/1A) (Omron brand) |
G |
|
|
|
|
| SSR voltage output (12VDC/30mA) |
X3/X5 |
|
|
|
|
| linear current 4-20mA output (X5 has own isolated power) |
K1/K3 |
|
|
|
|
| thyristor zero crossing trigger output (K1: single-phase, K3: three-phase) |
K5/K6 |
|
|
|
|
| single-phase thyristor phase-shift trigger output (K5: 220V, K6: 380V) |
Alarm (ALM) | L0 |
|
|
|
| large volume relay contact output (250VAC/2A) (Chinese brand) |
L3 |
|
|
|
| dual channel N/O relay contact output (250VAC/2A) (Chinese brand) |
G |
|
|
|
| SSR voltage output (12VDC/30mA) |
| L1 |
|
| large volume relay contact output (250VAC/2A) (Chinese brand) |
L3 |
|
| dual channel N/O relay contact output (250VAC/2A) (Chinese brand) |
G |
|
| SSR voltage output (12VDC/30mA) |
Communication (COMM) | S/S4 |
| RS485 communication interface (S4 has own isolate power supply) |
Shell material | -UL | with UL standard certificate, flame retardant shell |
ATTENTION:
1. D size doesn’t have MIO, and its COMM and ALM share one slot. If controller installs RS485 module, it doesn’t have ALM; If controller requires alarm function it can install alarm module in AUX.
2. D2 size doesn’t have MIO and ALM, and its COMM and AUX share one slot. So controller should choose either RS485 or alarm function. If require both RS485 and alarm, users should choose D6 size which supports module SL. D2 size doesn’t support 0~5V/ 1~5V linear current input. Users can transform the signal into 0~500mV/ 100~500mA or choose D6 size.
3. About MIO: it supports 4~20mA/ 0~20mA input or signals from 2-wire transmitter when installing I4 module. Yudian instruments support thermocouple and RTD input a